Facility teams are being asked more often to prove that indoor air is healthy. Many start with a single CO2 number. That is understandable, and it is usually where the trouble begins, because no one number can tell you whether a building's air is good.

Each measurement answers a different question. Here is what the main ones tell you, what published guidance actually says, and how to set alert levels your team can use.

CO2 tells you about ventilation, not overall air quality

People exhale CO2, so it rises as a room fills and falls as fresh air replaces it. That makes it a useful indicator of whether ventilation is keeping up with occupancy.

It is often misread. You will frequently hear that 1,000 ppm is the limit. In its position on indoor carbon dioxide, updated in 2023, ASHRAE says that claim is incorrect for Standard 62.1, and that indoor CO2 concentrations do not provide an overall indication of indoor air quality. ASHRAE also notes that readings far above expected ranges may mean the ventilation system is not working properly.

The regulatory ceiling is much higher and is about worker exposure rather than comfort: OSHA's permissible exposure limit is 5,000 ppm as an 8-hour time-weighted average.

The practical approach is to learn what is normal for each room, then investigate when readings move away from normal.

Particles are a separate problem

A well-ventilated room beside a busy road can have low CO2 and high particle counts. PM2.5 and PM10 come in from outdoors and from activity inside the building.

No US limit applies specifically to office air, so many teams use the World Health Organization's 2021 air quality guidelines as a reference. They are written for ambient air: 5 µg/m³ as an annual mean and 15 µg/m³ as a 24-hour mean for PM2.5, and 15 µg/m³ and 45 µg/m³ for PM10.

Comparing zones is often more useful than any single figure. A rising reading in one zone tends to point to a filter or a local source.

Treat TVOC as a trend

Volatile organic compounds come from cleaning products, paints, furniture and stored materials. The US EPA notes that concentrations of many VOCs are consistently higher indoors than outdoors, up to ten times higher, and that no federally enforceable standards have been set for VOCs in non-industrial settings.

Sensors report a combined TVOC signal rather than individual chemicals, so the reading is best used to spot change: after a renovation, a new cleaning contractor or a delivery of new furniture.

Keep humidity and temperature in view

EPA advises keeping indoor humidity between 30 and 50 percent. Temperature and humidity are also what occupants notice first, so a logged history gives you context when complaints arrive.

How to set alert levels that work

Because the published references are not office action levels, the most useful thresholds come from your own building.

  1. Collect two to four weeks of readings across normal working days before setting anything.
  2. Compare by room type. A boardroom and an open-plan floor behave differently.
  3. Alert on sustained change, not spikes. CO2 rising during a full meeting is expected. CO2 that stays high after a room empties, or high readings in a lightly used room, points to ventilation.
  4. Pair air data with occupancy, so you can separate a full room from a fault.
  5. Send each alert to the person who can fix it, and keep the history for your next review.

Good indoor air management is less about hitting one number and more about knowing what normal looks like in your building, and noticing quickly when it changes.